abstract
- © The Author(s) 2021.A numerical heat and mass transfer model with thermophysical properties dependent on the temperature, humidity ratio and atmospheric pressure was developed. The numerical model was verified and validated against literature, and it showed good agreements. The pseudo-transient model provides a low-cost computational tool to evaluate the potential and performance of a dew point evaporative cooling system for a wide range of extreme climate conditions (BWh, BSh, Cw and Aw from Köppen classification). A parametric analysis of different operational and design conditions in the evaporative cooler was conducted. Results show that there is an optimal channel length for given climatic conditions. The Dew-point evaporative cooling (DPEC) system showed that the best thermal performance corresponds to the climate very arid (Hermosillo ¿ BWh) with 4018 comfort hours (83.1%) followed by the climate arid (Monterrey ¿ BSh) with 3470 comfort hours (90.9%), the mild climate (Puebla ¿ Cw) with 295 comfort hours (100%) and the warm climate (Cancun ¿ Aw) with 3452 comfort hours (62.3%). Finally, an engineering correlation for constant atmospheric pressure and channel length was obtained ((Formula presented.) of 93%).